6 |
Description
From:
The DLS-75 Power Converter/Battery Charger converts 108-132V AC to 13.4V DC for both DC load operation such as when programming on-boad vehicle modules and 12V battery charging. As a power supply, the unit's tightly controlled regulation allows the user to operate a nominal 12VDC load up to 75 amps. In battery charger mode, the unit will maintain the battery, delivering its full-rated current when the battery capacity falls sufficiently low. The voltage is set to deliver maximum current for the necessary period of time to minimize undue stress to the battery caused by heating of its cells. Over time, as the battery nears its full capacity, the DLS-75 will automatically lower the current, providing a proper float-charge to the battery to prevent self-discharge of the cells. The unit features a Dual Voltage Jack that can trigger a step up of the output DC voltage from 13.5 to 14.2. Ratings and specifications: DC Output Voltage (No Load): 13.6V Output Voltage Tolerance: + / - .7% Output Amperage, MAX Continuous: 75 AMPS Output Voltage (Full Load): 13.4V Maximum Power Output, Continuous: 1000 Watts Ripple and Noise: <100mV rms Input Voltage Range: 108 - 132 AC Input Voltage Frequency: 47 - 63 Hz Maximum AC Current (at 108Vac): 18.2 Amps Maximum Inrush Current, Single Cycle: 40 Amps Short Circuit Protection: Yes Overload Protection: > 100% Line Regulation: 100 mV rms Load Regulation: <1.5% Fan Control: Proportional Thermal Protection: YES Working Temperature Range: 0° to 40° C Storage Temperature: -20° to 80° C Approximate Dimensions: 13" x 6.5" x 3.4" Weight: 4.5 lbs
To:
The DLS-75 Power Converter/Battery Charger converts 108-132V AC to 13.4V DC for both DC load operation such as when programming on-boad vehicle modules and 12V battery charging. As a power supply, the unit's tightly controlled regulation allows the user to operate a nominal 12VDC load up to 75 amps. In battery charger mode, the unit will maintain the battery, delivering its full-rated current when the battery capacity falls sufficiently low. The voltage is set to deliver maximum current for the necessary period of time to minimize undue stress to the battery caused by heating of its cells. Over time, as the battery nears its full capacity, the DLS-75 will automatically lower the current, providing a proper float-charge to the battery to prevent self-discharge of the cells. The unit features a Dual Voltage Jack that can trigger a step up of the output DC voltage from 13.5 to 14.2. Ratings and specifications: DC Output Voltage (No Load): 13.6V Output Voltage Tolerance: + / - .7% Output Amperage, MAX Continuous: 75 AMPS Output Voltage (Full Load): 13.4V Maximum Power Output, Continuous: 1000 Watts Ripple and Noise: <100 mV rms Input Voltage Range: 108 - 132 AC Input Voltage Frequency: 47 - 63 Hz Maximum AC Current (at 108Vac): 18.2 Amps Maximum Inrush Current, Single Cycle: 40 Amps Short Circuit Protection: Yes Overload Protection: > 100% Line Regulation: 100 mV rms Load Regulation: <1.5% Fan Control: Proportional Thermal Protection: YES Working Temperature Range: 0° to 40° C Storage Temperature: -20° to 80° C Approximate Dimensions: 13" x 6.5" x 3.4" Weight: 7.8 lbs
Last Modified:
|
The DLS-75 Power Converter/Battery Charger converts 108-132V AC to 13.4V DC for both DC load operation such as when programming on-boad vehicle modules and 12V battery charging. As a power supply, the unit's tightly controlled regulation allows the user to operate a nominal 12VDC load up to 75 amps. In battery charger mode, the unit will maintain the battery, delivering its full-rated current when the battery capacity falls sufficiently low. The voltage is set to deliver maximum current for the necessary period of time to minimize undue stress to the battery caused by heating of its cells. Over time, as the battery nears its full capacity, the DLS-75 will automatically lower the current, providing a proper float-charge to the battery to prevent self-discharge of the cells. The unit features a Dual Voltage Jack that can trigger a step up of the output DC voltage from 13.5 to 14.2. Ratings and specifications: DC Output Voltage (No Load): 13.6V Output Voltage Tolerance: + / - .7% Output Amperage, MAX Continuous: 75 AMPS Output Voltage (Full Load): 13.4V Maximum Power Output, Continuous: 1000 Watts Ripple and Noise: <100mV rms Input Voltage Range: 108 - 132 AC Input Voltage Frequency: 47 - 63 Hz Maximum AC Current (at 108Vac): 18.2 Amps Maximum Inrush Current, Single Cycle: 40 Amps Short Circuit Protection: Yes Overload Protection: > 100% Line Regulation: 100 mV rms Load Regulation: <1.5% Fan Control: Proportional Thermal Protection: YES Working Temperature Range: 0° to 40° C Storage Temperature: -20° to 80° C Approximate Dimensions: 13" x 6.5" x 3.4" Weight: 4.5 lbs |
The DLS-75 Power Converter/Battery Charger converts 108-132V AC to 13.4V DC for both DC load operation such as when programming on-boad vehicle modules and 12V battery charging. As a power supply, the unit's tightly controlled regulation allows the user to operate a nominal 12VDC load up to 75 amps. In battery charger mode, the unit will maintain the battery, delivering its full-rated current when the battery capacity falls sufficiently low. The voltage is set to deliver maximum current for the necessary period of time to minimize undue stress to the battery caused by heating of its cells. Over time, as the battery nears its full capacity, the DLS-75 will automatically lower the current, providing a proper float-charge to the battery to prevent self-discharge of the cells. The unit features a Dual Voltage Jack that can trigger a step up of the output DC voltage from 13.5 to 14.2. Ratings and specifications: DC Output Voltage (No Load): 13.6V Output Voltage Tolerance: + / - .7% Output Amperage, MAX Continuous: 75 AMPS Output Voltage (Full Load): 13.4V Maximum Power Output, Continuous: 1000 Watts Ripple and Noise: <100 mV rms Input Voltage Range: 108 - 132 AC Input Voltage Frequency: 47 - 63 Hz Maximum AC Current (at 108Vac): 18.2 Amps Maximum Inrush Current, Single Cycle: 40 Amps Short Circuit Protection: Yes Overload Protection: > 100% Line Regulation: 100 mV rms Load Regulation: <1.5% Fan Control: Proportional Thermal Protection: YES Working Temperature Range: 0° to 40° C Storage Temperature: -20° to 80° C Approximate Dimensions: 13" x 6.5" x 3.4" Weight: 7.8 lbs |
|
Scott Brown |
5 |
Description
From:
The DLS-75 Power Converter/Battery Charger converts 108-132v AC to 13.4v DC for both DC load operation such as when programming on-boad vehicle modules and 12V battery charging. As a power supply, the unit's tightly controlled regulation allows the user to operate a nominal 12VDC load up to 75 amps. In battery charger mode, the unit will maintain the battery, delivering its full-rated current when the battery capacity falls sufficiently low. The voltage is set to deliver maximum current for the necessary period of time to minimize undue stress to the battery caused by heating of its cells. Over time, as the battery nears its full capacity, the DLS-75 will automatically lower the current, providing a proper float-charge to the battery to prevent self-discharge of the cells. The unit features a Dual Voltage Jack that can trigger a step up of the output DC voltage from 13.5 to 14.2.
To:
The DLS-75 Power Converter/Battery Charger converts 108-132V AC to 13.4V DC for both DC load operation such as when programming on-boad vehicle modules and 12V battery charging. As a power supply, the unit's tightly controlled regulation allows the user to operate a nominal 12VDC load up to 75 amps. In battery charger mode, the unit will maintain the battery, delivering its full-rated current when the battery capacity falls sufficiently low. The voltage is set to deliver maximum current for the necessary period of time to minimize undue stress to the battery caused by heating of its cells. Over time, as the battery nears its full capacity, the DLS-75 will automatically lower the current, providing a proper float-charge to the battery to prevent self-discharge of the cells. The unit features a Dual Voltage Jack that can trigger a step up of the output DC voltage from 13.5 to 14.2. Ratings and specifications: DC Output Voltage (No Load): 13.6V Output Voltage Tolerance: + / - .7% Output Amperage, MAX Continuous: 75 AMPS Output Voltage (Full Load): 13.4V Maximum Power Output, Continuous: 1000 Watts Ripple and Noise: <100mV rms Input Voltage Range: 108 - 132 AC Input Voltage Frequency: 47 - 63 Hz Maximum AC Current (at 108Vac): 18.2 Amps Maximum Inrush Current, Single Cycle: 40 Amps Short Circuit Protection: Yes Overload Protection: > 100% Line Regulation: 100 mV rms Load Regulation: <1.5% Fan Control: Proportional Thermal Protection: YES Working Temperature Range: 0° to 40° C Storage Temperature: -20° to 80° C Approximate Dimensions: 13" x 6.5" x 3.4" Weight: 4.5 lbs
Last Modified:
|
The DLS-75 Power Converter/Battery Charger converts 108-132v AC to 13.4v DC for both DC load operation such as when programming on-boad vehicle modules and 12V battery charging. As a power supply, the unit's tightly controlled regulation allows the user to operate a nominal 12VDC load up to 75 amps. In battery charger mode, the unit will maintain the battery, delivering its full-rated current when the battery capacity falls sufficiently low. The voltage is set to deliver maximum current for the necessary period of time to minimize undue stress to the battery caused by heating of its cells. Over time, as the battery nears its full capacity, the DLS-75 will automatically lower the current, providing a proper float-charge to the battery to prevent self-discharge of the cells. The unit features a Dual Voltage Jack that can trigger a step up of the output DC voltage from 13.5 to 14.2. |
The DLS-75 Power Converter/Battery Charger converts 108-132V AC to 13.4V DC for both DC load operation such as when programming on-boad vehicle modules and 12V battery charging. As a power supply, the unit's tightly controlled regulation allows the user to operate a nominal 12VDC load up to 75 amps. In battery charger mode, the unit will maintain the battery, delivering its full-rated current when the battery capacity falls sufficiently low. The voltage is set to deliver maximum current for the necessary period of time to minimize undue stress to the battery caused by heating of its cells. Over time, as the battery nears its full capacity, the DLS-75 will automatically lower the current, providing a proper float-charge to the battery to prevent self-discharge of the cells. The unit features a Dual Voltage Jack that can trigger a step up of the output DC voltage from 13.5 to 14.2. Ratings and specifications: DC Output Voltage (No Load): 13.6V Output Voltage Tolerance: + / - .7% Output Amperage, MAX Continuous: 75 AMPS Output Voltage (Full Load): 13.4V Maximum Power Output, Continuous: 1000 Watts Ripple and Noise: <100mV rms Input Voltage Range: 108 - 132 AC Input Voltage Frequency: 47 - 63 Hz Maximum AC Current (at 108Vac): 18.2 Amps Maximum Inrush Current, Single Cycle: 40 Amps Short Circuit Protection: Yes Overload Protection: > 100% Line Regulation: 100 mV rms Load Regulation: <1.5% Fan Control: Proportional Thermal Protection: YES Working Temperature Range: 0° to 40° C Storage Temperature: -20° to 80° C Approximate Dimensions: 13" x 6.5" x 3.4" Weight: 4.5 lbs |
|
Scott Brown |
4 |
Name
From:
DLS-75 Power Converter/Battery Charger
To:
DLS-75 Power Converter / Battery Charger
Last Modified:
|
DLS-75 Power Converter/Battery Charger |
DLS-75 Power Converter / Battery Charger |
|
Scott Brown |
3 |
Description
From:
The DLS-75 Power Converter/Battery Charger converts 108-132v AC to 13.4v DC for both DC load operation such as when programming on-boad vehicle modules and 12V battery charging. As a power supply, the unit's tightly controlled regulation allows the user to operate a nominal 12VDC load up to 75 amps. In battery charger mode, the unit will maintain the battery, delivering its full-rated current when the battery capacity falls sufficiently low. The voltage is set to deliver maximum current for the necessary period of time to minimize undue stress to the battery caused by heating of its cells. Over time, as the battery nears its full capacity, the DLS-75 will automatically lower the current, providing a proper float-charge to the battery to prevent self-discharge of the cells. The unit features a Dual Voltage Jack that can trigger the unit to step up the output DC voltage from 13.5 to 14.2.
To:
The DLS-75 Power Converter/Battery Charger converts 108-132v AC to 13.4v DC for both DC load operation such as when programming on-boad vehicle modules and 12V battery charging. As a power supply, the unit's tightly controlled regulation allows the user to operate a nominal 12VDC load up to 75 amps. In battery charger mode, the unit will maintain the battery, delivering its full-rated current when the battery capacity falls sufficiently low. The voltage is set to deliver maximum current for the necessary period of time to minimize undue stress to the battery caused by heating of its cells. Over time, as the battery nears its full capacity, the DLS-75 will automatically lower the current, providing a proper float-charge to the battery to prevent self-discharge of the cells. The unit features a Dual Voltage Jack that can trigger a step up of the output DC voltage from 13.5 to 14.2.
Last Modified:
|
The DLS-75 Power Converter/Battery Charger converts 108-132v AC to 13.4v DC for both DC load operation such as when programming on-boad vehicle modules and 12V battery charging. As a power supply, the unit's tightly controlled regulation allows the user to operate a nominal 12VDC load up to 75 amps. In battery charger mode, the unit will maintain the battery, delivering its full-rated current when the battery capacity falls sufficiently low. The voltage is set to deliver maximum current for the necessary period of time to minimize undue stress to the battery caused by heating of its cells. Over time, as the battery nears its full capacity, the DLS-75 will automatically lower the current, providing a proper float-charge to the battery to prevent self-discharge of the cells. The unit features a Dual Voltage Jack that can trigger the unit to step up the output DC voltage from 13.5 to 14.2. |
The DLS-75 Power Converter/Battery Charger converts 108-132v AC to 13.4v DC for both DC load operation such as when programming on-boad vehicle modules and 12V battery charging. As a power supply, the unit's tightly controlled regulation allows the user to operate a nominal 12VDC load up to 75 amps. In battery charger mode, the unit will maintain the battery, delivering its full-rated current when the battery capacity falls sufficiently low. The voltage is set to deliver maximum current for the necessary period of time to minimize undue stress to the battery caused by heating of its cells. Over time, as the battery nears its full capacity, the DLS-75 will automatically lower the current, providing a proper float-charge to the battery to prevent self-discharge of the cells. The unit features a Dual Voltage Jack that can trigger a step up of the output DC voltage from 13.5 to 14.2. |
|
Scott Brown |
2 |
Image
From:
To:
Last Modified:
|
|
|
|
Scott Brown |
1 |
Page Created
|
|
|
|
Scott Brown |